RO30A NH00C gG HRC Knife‑Blade Fuse Link, Compact Size for MCC & Switch Cabinet Circuit Protection

24 Hours online(Perfessional response)

facebookinstagramtiktokyoutubeX

The MIRO RO30A NH00C compact square‑tube knife‑blade HRC fuse link features overall dimensions of 120 × 53 × 35 mm. It belongs to gG general‑purpose utilization category for cable and circuit protection. Compliant with IEC 60269‑2 and GB/T 13539.2 standards, rated AC 500V/690V. Breaking capacity reaches 120kA at 500V and 50kA at 690V, current range covers 6‑125A. Compact plug‑in knife‑blade design fits all NH00C series fuse bases for fast replacement. Widely used in low‑voltage MCC motor control centers and compact industrial power distribution cabinets.

    Date sheet

    MIRO RO30A (NH00C) measures 78 × 49 × 48 mm, it is a gG category knife‑blade fuse link, rated voltage 500V/660V, breaking capacity up to 120kA at 500V and 50kA at 690V, current range 4‑100A, square‑tube knife‑blade plug‑in installation.

    This product is fully matched with mainstream international brands in electrical performance and installation dimension for direct replacement, no cabinet or base modification required:

    1. Replaceable for Mersen NH00C gG series with identical voltage, breaking capacity and dimension, directly compatible with original fuse base;
    2. Interchangeable with Eaton NH00C series, same gG utilization category and universal plug‑in structure;
    3. Direct substitute for Littelfuse NH00C‑Style knife‑blade fuse, identical electrical parameters and physical dimension for seamless retrofit;
    4. Replacement for Siemens 3NA2 series, fits existing switchgear without mechanical alteration;
    5. Drop‑in alternative for Bussmann NHG00C‑690 fuse with equivalent protection performance.

    Application scenario: Overload and short‑circuit protection for cables and circuits in motor control centers(MCC), compact low‑voltage cabinets and industrial power distribution systems.

     low‑voltage cabinets and industrial power distribution systems.

    parameter value Test standard/ method
    Frequency 45-62Hz Adopt network analyzer for testing
    Voltage 500V/690V Voltmeter
    Current 16A,20A,25A,32A,40A,50A,63A,80A,100A Ammeter, clamp meter
    Breaking capacity of a fuse-link 500V/100kA
    690V/50kA
    Type test
    Utilization category(of a fuse link) aR GB 13539.1-2008
    GB/T 13539.4-2009
    Installation method Square tube knife plug-in type -
    Others - -

    PRODUCTS SIZE:

    Parameter Value Test standard/method
    Frequency 45‑62Hz Test by network analyzer
    Rated working Voltage 500V/690V Voltmeter
    Rated working Current 500V: 2A,4A,6A,8A,10A,16A,20A,25A,32A,40A,50A,63A,80A,100A
    690V: 2A,4A,6A,8A,10A,16A,20A,25A,32A,40A,50A,63A
    Ammeter, clamp meter
    Power dissipation of a fuse‑link 12W max Millivoltmeter
    Breaking capacity of a fuse‑link 500V/100kA
    690V/50kA
    Type test
    Utilization category of a fuse‑link gG GB 13539.1‑2015
    GB/T 13539.2‑2015
    Installation method Square‑tube knife‑blade plug‑in type ‑

    Applications

    Protection against overload and short-circuit in electric lines (type gG), also available for protection of semiconductor parts and equipments against short-circuit (type aR) and protection of motors (type aM).

    Design Features

    Variable cross-section fuse element made from pure copper or silver sealed in cartridge made from high-duty ceramic; Fuse tube filled with chemically treated high-purity quartz sand as arc extinguishing medium. Dot-welding of fuse element ends to the terminals ensures reliable electric connection and forms insert knife type contacts. Indicator or striker may be attached to the fuse link to show cutout of fuse or to give various signals and to cut the circuit automatically.